Redundant Power Supply Sequencer Module (RPSSM)
P-10 Installation and Use Revised Nov-2010
Specifications
Redundant Power Supply Sequencer Module
Input Range:
22.2 to 30V DC (24V input supply, nominal)
Shutdown occurs at 22.2 nominal for 24V
input supply systems, respectively.
Temperature Range:
Operating: -40 to 85
o
C
Storage: -40 to 85
o
C
Relative Humidity:
15 to 95% non-condensing
Vibration:
1G for 10-150 Hz
0.5 G for 150 Hz to 2000 Hz
RFI Susceptibility
3V/m 80 MHz to 1000 MHz per EN50082-2
Watchdog MOSFET
1A
Power Supplies (1 or 2 on the RPSSM)
Input Range
20 to 30Vdc (24V input supply, nominal)
Output Voltage
5V ± 2%, 3.3V ± 2%
Output Current
1A @ 3.3V, 2A @5V
Efficiency
80% at full load
Fusing
7x2 mm fuse 3A fast acting
Field Supply Power
VINF Input Range
20V to 30V
Fusing
5x20 mm fuse 10A slow blow