EasyManuals Logo
Home>Emerson>Controller>Tescom ER5050

Emerson Tescom ER5050 User Manual

Emerson Tescom ER5050
248 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #239 background imageLoading...
Page #239 background image
ER5000
239
Certications and Warranty
CE
Conforms to all known European Union
requirements.
EMC DIRECTIVE 2014/30/EU
IEC/EN 61000-6-2: 2005
IEC/EN 61000-6-4: 2007/A1:2011
FM
Is not certied but conforms to FM
Standards. FM Class 3600-1998 & FM Class
3615-2006
SPECIAL CONDITIONS FOR SAFE USE:
Make sure everything is properly
assembled before powering.
Do not open when an explosive
atmosphere is present.
Installation to be in accordance with the
latest edition of National Electrical Code.
The cable and conduit entry devices
shall be certied ame proof types,
suitable for the conditions of use and
correctly installed.
Unused conduit entry must be closed
with suitable blanking element.
Seal conduit entry within 18 inches.
Rated for 20.5 to 28.5 VDC,
340 mAmps.
Max working pressure: 110 PSIG
-20°C ≤ T
amb
≤ 60°C
Thread entry sizes are 1/8" - 27 NPT
and 1/2" - 14 NPT. Reference page 18
for locations.
The user/installer shall not remove any
of the three, 1/8”-27 NPT plugs that
are tted into the base of the enclosure
as this will invalidate the Hazardous
Location Certication. Reference
page 18 for locations.
Hazardous Locations Special Requirements and Certification for the ER5050
Copies of all certication documents are available at www.tescom.com. Click on the CERTIFICATIONS Quick Link.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Tescom ER5050 and is the answer not in the manual?

Emerson Tescom ER5050 Specifications

General IconGeneral
BrandEmerson
ModelTescom ER5050
CategoryController
LanguageEnglish

Related product manuals