7 Protection Parameter Settings
This setting is used to enable (activate) or disable (turn off) the CB Open Supervision function
0.05s to 1.0s steps 0.01s
This setting is used to define the circuit breaker opening time threshold.
6. CB Open Alarm Enabled Enabled / Disabled
This setting is used to enable (activate) or disable (turn off) the CB Open Alarm function.
7. CB Open Oper 2000 1 to 30000 step 1
This setting is used to define the threshold for number of CB open operations and an alarm is issued once this threshold is crossed.
Disabled / Local/Remote / Local + Remote
This setting selects the type of circuit breaker control to be used.
9. Close Pulse Time 0.50 S 0.1s to 50s step 0.01s
This setting defines duration of the close pulse within which the CB should close after a close command is issued
10. Open Pulse Time 0.50 S 0.1s to 50s step 0.01s
This setting defines the duration of the trip pulse within which the CB should trip when a manual or protection trip command is issued
2.3 DATE AND TIME Settings
1. Password 0000 0000 to zzzz
This setting specifies to enter the set password.
2. Local Time Enable Fixed Fixed / Flexible / Disabled
Setting to turn on/off local time adjustments.
Fixed - A local time zone adjustment can be defined using the Local Time offset setting and all interfaces will use local time.
Flexible - A local time zone adjustment can be defined using the Local Time offset setting and each interface can be assigned to the UTC
zone or local time zone with the exception of the local interfaces which will always be in the local time zone.
Disabled - No local time zone will be maintained. Time synchr
onization from any interface will be used to directly set the master clock and
all displayed (or read) times on all interfaces will be based on the master clock with no adjustment.
3. Local Time Offset 0 Mins -720 to + 720 step 15 mins
Setting to specify an offset for local time zone from -12 to +12 hrs in 15 minute intervals. This adjustment is applied to the time based on
UTC/GMT master clock.
4. DST Enable Enabled Enabled / Disabled
Setting to turn on/off daylight saving time adjustment to local time.
5. DST Offset 60 Mins 30 mins, 60 mins
Setting to specify daylight saving offset used for the local time adjustment.
First / Second / Third / Fourth / Last
Setting to specify the week of the month in which daylight saving time adjustment starts
7. DST Start Day Sunday
Sunday / Monday / Tuesday / Wednesday / Thursday /
Friday/ Saturday
Setting to specify the day of the week in which daylight saving time adjustment starts
8. DST Start Month March
January / February / March / April / May / June / July /
August / September / October / November / December
Setting to specify the month in which daylight saving time adjustment starts
9. DST Start Mins 60 Mins 0 to 1425 mins step 15mins.
Setting to specify the time of day in which daylight saving time adjustment starts. This is set relative to 00:00 hrs on the selected day
when time adjustment is to start
10. DST End Last First / Second / Third / Fourth / Last
Setting to specify the week of the month in which daylight saving time adjustment ends