I2/I1 Time Dly-1
10.00S
By using the (5) or (6) key, I2/I1 Time Dly-1 can be set. The setting
range is from 0 to 100s in steps of 0.01s.
BC Trip
Enabled
Editable setting
By using the (5) or (6) key, BC Trip is Enabled.
I2/I1Set-2
0.50
Editable setting
By using the (5) or (6) key, I2/I1 Set-2 can be set. The setting range is
from 0.20 to 1.00 in steps of 0.01
I2/I1 Time Dly-2
10.00S
By using the (5) or (6) key, I2/I1 Time Dly-2 can be set. The setting
range is from 0 to 100s in steps of 0.01s.
2.3.16.6 Group 1 – Earth Fault 1 Submenu
2.3.16.6.1
Edit Settings
(if IN1>1 Function, IN1>2 Function and IN1>3 Function are disabled)
GROUP 1
Password protected window for
settings:
SYSTEM CONFIG, OVERCURRENT, NEG SEQUENCE O/C, BROKEN
CONDUCTOR, EARTH FAULT 1, EARTH FAULT 2, THERMAL
OVERLOAD, COLD LOAD PICKUP, UNDERCURRENT and CB FAIL.
Note: Group 1 Setting will be seen only when it is enabled in
Configuration setting.
EARTH FAULT 1
Password protected window for Earth Fault 1 (measured) i.e. IN1>1
Function, IN1>2 Function and IN1>3 Function can be set as Disabled /
DT / IEC S Inverse/ S Inverse (1.3Sec)/ IEC V Inverse/ IEC E Inverse/
UK LT Inverse /IEEE M Inverse/ IEEE V Inverse/ IEEE E Inverse /US
Inverse /US ST Inverse
Measured
Read-only
Description for Earth Fault 1
IN1>1Function
Disabled
Editable setting
By using the (5) or (6) key, IN1>1 Function is Disabled.
IN1>2Function
Disabled
By using the (5) or (6) key, IN1>2 Function is Disabled.