EasyManuals Logo
Home>GE>Relays>Agile P153

GE Agile P153 User Manual

GE Agile P153
268 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #70 background imageLoading...
Page #70 background image
P50 Agile P153
5 Configuration
P153/EN M/B
5-32
2.3.14 Disturbance Record Menu
2.3.14.1 View/Edit Settings
DISTURBANCE REC
Password protected window for
“Disturbance Record”
settings:
Trigger Position
Trigger Position
50%
Editable setting
By using the (+ /5) or (- /6) key, the desired Trigger Position can be
set. The setting range is from 10% to 90% in steps of 1.
2.3.15 Commissioning Test Menu
2.3.15.1 View/Edit Settings
COMMISSION. TEST
Password protected window for “Commissioning Test” settings:
Test Mode, Test Pattern, Contact Test and Test LEDs.
Test Mode
Disabled
Editable setting
By using the (5) or (6) key, Test Mode be set as Disabled/Test
Mode/Contacts Blocked.
Test Pattern
0000
Editable setting
By using the (5) or (6) key, Test Pattern can be set.
Setting ‘1’ means that output relay contact will be tested when the
Contact Test cell is set to Apply Test.
Setting ‘0’ means that output relay contact will not be tested when the
Contact Test cell is set to Apply Test.
Eg: Setting 1010 will operate RL4 & RL2 during Contact test
Contact Test
No Operation
Editable setting
By using the (5) or (6) key, Contact Test can be set for No Operation
/ Apply Test / Remove Test

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Agile P153 and is the answer not in the manual?

GE Agile P153 Specifications

General IconGeneral
BrandGE
ModelAgile P153
CategoryRelays
LanguageEnglish

Related product manuals