2.3.8 Configuration Menu
2.3.8.1 View/Edit Settings
CONFIGURATION
Password protected window for “CONFIGURATION’’
Restore Defaults, Active Settings, Copy From, Copy To, Setting Group 1
(Enabled/Disabled), Setting Group 2 (Enabled/Disabled), System Config
(Enabled/Disabled), Overcurrent (Enabled/Disabl
O/C (Enabled/Disabled), Broken Conductor (Enabled/Disabled), Earth
Fault 1 (Enabled/Disabled), Earth Fault 2 (Enabled/Disabled), Thermal
Overload (Enabled/Disabled), Cold Load Pickup (Enabled/Disabled),
Measure’t Setup, UnderCurr Prot (En
(Enabled/Disabled) and Setting Values.
Restore Defaults
No Operation
Editable setting
By using the (5) or (6) key, Restore Defaults can be set as No
Operation / All Settings / Setting Group 1 / Setting Group 2.
Active Settings
Group 1
By using the (5) or (6) key, Active Setting can be set as Group 1 /
Group 2.
Copy From
Group 1
Editable setting
By using the (5) or (6) key, Copy From can be set as Group 1 /
Group 2.
Copy To
No Operation
Editable setting
By using the (5) or (6) key, Copy To can be set as No Operation /
Group 1 / Group 2.
Setting Group 1
Enabled
By using the (5) or (6) key, Setting Group 1 can be Enabled or
Disabled.
Setting Group 2
Disabled
By using the (5) or (6) key, Setting Group 2 can be Enabled or
Disabled.
System Config
Disabled
Editable setting
By using the (5) or (6) key, System Configuration can be Enabled or
Disabled.