P50 Agile P153
5 Configuration
P153/EN M/B
5-60
EARTH FAULT 1
Password protected window for
Earth Fault 1
i.e. IN1>1 Function, IN1>2
Function and IN1>3 Function. The functions can be set as Disabled / DT
/ IDMT.
EARTH FAULT 2
Password protected window for Earth Fault 2 i.e. IN2>1 Function, IN2>2
Function and IN2>3 Function. The functions can be set as Disabled / DT
/ IDMT.
THERMAL OVERLOAD
Password protected window for Thermal Overload i.e. Characteristic
(Disabled/Single), Thermal Trip, Thermal Alarm, Time Constant 1 and K.
COLD LOAD PICKUP
Password protected window for
Cold Load Pickup
i.e. tcold Time Delay,
tclp Time Delay, I>1 Status, I>2 Status, I>3 Status, IN1>1 Status, IN1>2
Status, IN1>3 Status, IN2>1 Status, IN2>2 Status and IN2>3 Status
UNDERCURRENT
Password protected window for Undercurrent i.e. I< Status, I< and tI<.
CB FAIL
Password protected window for CB FAIL i.e. CB Fail Status, CB Fail
Timer, CB Reset, I<, IN<, Remove I> Start and Remove IN> Start.
Note: The Group 2 settings for System Configuration, Over Current, Negative Sequence O/C, Broken
Conductor, Earth Fault 1, Earth Fault 2, Thermal Overload, Cold Load Pkp Under Current
Protection and CB Fail settings are similar to Group 1.