5-272 C60 Breaker Protection System GE Multilin
5.8 INPUTS AND OUTPUTS 5 SETTINGS
5
The GOOSE analog input FlexAnalog values are available for use in other C60 functions that use FlexAnalog values.
5.8.13 IEC 61850 GOOSE INTEGERS
PATH: SETTINGS INPUTS/OUTPUTS IEC 61850 GOOSE UINTEGERS GOOSE UINTEGER INPUT 1(16)
The IEC 61850 GOOSE uinteger inputs feature allows the transmission of FlexInteger values between any two UR-series
devices. The following settings are available for each GOOSE uinteger input.
• UINTEGER 1 DEFAULT: This setting specifies the value of the GOOSE uinteger input when the sending device is
offline and the
UINTEGER 1 DEFAULT MODE is set to “Default Value”.This setting is stored as a 32-bit unsigned integer
number.
• UINTEGER 1 DEFAULT MODE: When the sending device is offline and this setting is “Last Known”, the value of the
GOOSE uinteger input remains at the last received value. When the sending device is offline and this setting value is
“Default Value”, then the value of the GOOSE uinteger input is defined by the UINTEGER 1 DEFAULT setting.
The GOOSE integer input FlexInteger values are available for use in other C60 functions that use FlexInteger values.
SOURCE ENERGY
(Positive and Negative Watthours,
Positive and Negative Varhours)
E
BASE
= 10000 MWh or MVAh, respectively
SOURCE POWER P
BASE
= maximum value of V
BASE
× I
BASE
for the +IN and –IN inputs
SOURCE VOLTAGE V
BASE
= maximum nominal primary RMS value of the +IN and –IN inputs
SYNCHROCHECK
(Max Delta Volts)
V
BASE
= maximum primary RMS value of all the sources related to the +IN and –IN inputs
GOOSE UINTEGER
INPUT 1
UINTEGER 1 DEFAULT:
1000
Range: 0 to 429496295 in steps of 1
MESSAGE
UINTEGER 1 DEFAULT
MODE: Default Value
Range: Default Value, Last Known
Table 5–34: GOOSE ANALOG INPUT BASE UNITS (Sheet 2 of 2)
ELEMENT BASE UNITS