CLC/TS 50131-3 Compliancy
In order to be compliant with the technical specification CLC/TS 50131-3 (Alarm systems – Control and
indicating equipment), the following guidelines must be taken into account :
Zone configuration types reporting a Hold-up alarm (event code 0) should :
- not be bypassable
- not have swinger shutdown enabled
All zone configuration types should be set for
- double-end-of-line configuration - 2EOL (as of loc 111 segment 3 option 2)
- fast loop response (as of loc 111 segment 3 option 1)
- swinger shutdown(*) enabled (as of loc 111 segment 3 option 6)
Entry/exit zone configuration types and Follower zone configuration types should be set for Force Arming
(as of loc 111 segment 2 option) in order to fulfil paragraph 12.6.6 of the technical specifications
The use of instant zones (zone configuration type 6) is not allowed in order to fulfil paragraph 8.2.4.3 of the
technical specifications
The entry time should not be more than 45 seconds (location 24)
The following options need to be enabled :
- keypad sounder for battery trouble (location 39 option 4)
- keypad sounder for expander trouble (location 39 option 8)
- first alarm logic (location 37 segment 6 option 4)
- log protection mode (location 37 segment 6 option 5)
- 6 digit user codes (location 41 option 1)
- keypad shutdown mode (location 41 option 5)
A warning device(**) should be protected by a tamper loop
Programmable outputs that are used for warning devices must operate for a minimum of 90 seconds and
a maximum of 15 minutes unless other requirements are demanded by local or national regulations.
(*)swinger shutdown counter (loc 38) should be set with a maximum value of 3.
(**)The BELL output should not be used to connect an internal warning device
Remarks :
All reportable events that are set will be processed. In the event of multiple events being
present simultaneously, all these events will be processed and notified.
The NX-4 provides one or more outputs to fulfill the requirements described in Table 9 of
the CLC/TS 50131-3. All options of Table 13 of the CLC/TS 50131-3 can be fulfilled.
The level of tamper protection fulfils the requirements for installations inside the
supervised premises
Indicators that share common means of annunciation will not apply any priorisation.
Maximum load taken from the AUX OUT should not exceed the values as stated in the
table below (EN-50131-6:1997 and EN50131-1:1997 table 16)
battery NX-4 NX-6 NX-8
Max current consumpt. 77mA 96mA 105mA
Max current AUX OUT 7.2Ah 480mA 460mA 450mA
Max current AUX OUT 18Ah 570mA 560mA 550mA
NX-4-EUR Installation manual Page 34 02/07/06

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE NX-4-EUR and is the answer not in the manual?

GE NX-4-EUR Specifications

General IconGeneral
BrandGE
ModelNX-4-EUR
CategoryControl Panel
LanguageEnglish

Related product manuals