20 ADV200 SP • Quick start up guide - Specification and installation
5.1 Power section
5.1.1 Cable Cross Section
Sizes
Terminals: L1 - L2 - L3 - BR1 - BR2 - C - D - U - V - W
Maximum Cable Cross Section
(flexible conductor)
Recommended
stripping
Tightening torque
(min)
(mm
2
) AWG (mm) (Nm)
1015
4 10 7 0.5 ... 0.6
1022
4 10 7 0.5 ... 0.6
1030
4 10 7 0.5 ... 0.6
1040
4 10 7 0.5 ... 0.6
1055
4 10 7 0.5 ... 0.6
2075
6 8 10 0.7 ... 0.8
2110
6 8 10 1.2 ... 1.5
2150
6 7 12 1.5 ... 1.7
3185
16 6 14 1.5 ... 1.7
3220
16 6 14 1.5 ... 1.7
3300
16 6 14 1.5 ... 1.7
4370
35 2 18 2.4 ... 4.5
4450
35 2 18 2.4 ... 4.5
4550
35 2 18 2.4 ... 4.5
5750
95
(BR1/BR2=50) 4/0 (BR1/BR2=1/0) 23 (BR1/BR2=27) 14 (BR1/BR2=10)
5900
95 4/0 23 14
51100
95 4/0 23 14
61320
150 300 30 24
61600
240 500 40 40
Sizes
Connection
on mechanical cabinet
Cable Cross Section Lock screw
diameter
Recommended
terminal
Tightening torque
(mm
2
) AWG / kcmil (mm) (mm) (Nm)
1015 ... 1030 16 AWG 6 M5 Eyelet - Spade 5
1040 ... 4550 16 AWG 6 M6 Eyelet - Spade 5
5750 ... 51100 50 AWG 1/0 M6 Eyelet - Spade 5
61320 75 AWG 2/0 M8 Eyelet - Spade 12
61600 120 250 kcmil M8 Eyelet - Spade 12