EasyManuals Logo
Home>gefran>DC Drives>ADV200 SP Series

gefran ADV200 SP Series User Manual

gefran ADV200 SP Series
106 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #46 background imageLoading...
Page #46 background image
46 ADV200 SP • Quick start up guide - Specification and installation
Note ! For further information, see chapter 8.2.
6.8 Saving and recovery of new parameter settings
󰀨

one drive to another.
6.8.1 Selection of the keypad memory
T+ T- EN LOC ILim n:0 AL
0 4.19
PA R: 594
Keypad memory select
Def: 1
T+ T-ENLOC ILim n:0 AL
01 MONITOR
02 DRIVE INFO
03 STARTUP WIZARD
04 DRIVE CONFIG
E
T+ T- EN LOC ILim n:0 AL
0 4.19
PA R: 594
Keypad memory select
Def: 1
1
000000002
Menu 04 parameter 04.21 , PAR : 594.
The keypad features 5 memory areas dedicated to saving parameters.
parameter.

6.8.2 Saving of parameters on the keypad
T+ T- EN LOC ILim n:0 AL
0 4.17
PA R: 590
Save par to keypad
PressEto execute
E
T+ T- EN LOC ILim n:0 AL
0 4.17
PA R: 590
DRIVE --> K2006 X
T+ T-ENLOC ILim n:0 AL
01 MONITOR
02 DRIVE INFO
03 STARTUP WIZARD
04 DRIVE CONFIG
X3
Menu 04 parameter 04.19 Save par to keypad, PAR : 590.
Is used to transfer the parameters from the drive to the selected keypad memory.
To start the operation, press the E key.

Instead of the letter X
-

If an error occurs during transfer, the following message is displayed:
T+ T- EN LOC ILim n:0 AL
Message
01
Save par failed
Press ESC to exit
Code: XX
The code XX indicates the type of error, see paragraph 8.2.
To exit from the error message, press the ESC key.
6.8.3 Load parameters from keypad
Menu 04 parameter 04.20 Load par from keypad, PAR : 592.
Is used to transfer the parameters from the selected memory of the keypad to the drive.
T+ T- EN LO C ILim n:0 AL
0 4.18
PA R: 592
Load par from keypad
PressEto execute
E
T+ T- EN LO C ILim n:0 AL
0 4.18
PA R: 592
DRIVE <-- K2006 X
T+ T-ENLOC ILim n:0 AL
01 MONITOR
02 DRIVE INFO
03 STARTUP WIZARD
04 DRIVE CONFIG
X2
To start the operation, press the E -
eration.
Instead of the letter X
-


Table of Contents