ADV200 SP • Quick start up guide - Specification and installation 51
7.1 Startup Wizard and dedicated settings
Only for isolated PV systems.
Introduction
The ADV200 SP can operate with regulation modes : V/f control (Voltage/Frequency) and Flux vector OL (open
loop).
Menu 04 parameter 04.2 Regulation mode, PAR: 552, default=V/f control.
Start-up in one mode is valid also for the other regulation modes.
The startup wizard is a guided procedure used for quick start-up of the drive that helps to set the main param-
eters.
It consists of a series of questions relating to the various sequences for entering and calculating the param-
eters necessary for correct drive operation.
The order of these sequences is as follows:
See step 1
Setting motor parameters See step 2
Self-tuning with rotating motor See step 3A
Self-tuning with motor at stand-still or coupled to the load
See step 3B
Setting the maximum speed reference value See step 4
Setting ramp parameters See step 5
Skip “Motopotentiometer, Jog and Braking resistor” settings
Saving parameters See step 6
Calibrate the parameters required for V/f control See step 7
Basic application settings See step 8
Application parametrization See step 9
Enable system / Checks See step 10
Saving parameters See step 11
The format of the function selection page is as follows:
T+ T-ENLOC ILim n:0 AL
01 MONITOR
02 DRIVE INFO
03 STARTUP WIZARD
04 DRIVE CONFIG
T+ T- EN LO C ILim n:0 AL
STARTUP WIZARD
Set motor data ?
E=Yes Down=Next
To terminate the sequence of functions and return to the menu, press the ESC key.
The end of the start-up sequence is indicated with the page:
T+ T- EN LO C ILim n:0 AL
STARTUP WIZARD
End of se
q
uence !
U
p
=Back Down=Next
Note ! In the procedures described below, the settings have been made using the ADV2075 drive and a 10 Hp (7.36 kW)
asynchronous motor.