ADV200 SP • Quick start up guide - Specification and installation 77
9.7
Voltage level of the inverter for safe operations
The minimum time SP
which an operator can operate on internal parts of the drive, without the danger of electric shock, is 5 minutes.
+10%, without any options
(time indicated
9.8 Cooling
All the Drives have internal fans.
Sizes
Dissipated power
Dissipated power
(ADV200 SP-EH
models)
Airflow of fan
(W) (W)
Heatsink (m
3
/h) Internal (m
3
/h)
1015 60 - 32 26
1022 90 - 32 32
1030 100 - 32 32
1040 120 - 32 32
1055 160 - 32 32
2075 200 - 32 32
2110 250 107,5 56 x 2 32
2150 300 118 56 x 2 32
3185 380 130 80 x 2 32
3220 460 - 80 x 2 32
3300 600 151 80 x 2 32
4370 900 218 2 x 250 2 x 50
4450 1000 235 2 x 250 2 x 50
4550 1290 255 2 x 250 2 x 50
5750 1760 293 2 x 285 1 x 170
5900 2150 430 2 x 355 2 x 170
51100 2400 520 2 x 355 2 x 170
61320 2850 - 3 x 310 2 x 170
61600 3600 - 3 x 310 2 x 170
9.9 Weight and dimensions
Sizes
ADV200 SP-...-4
ADV200 SP-EH-...-4
Weight (kg) Weight (lbs) Sizes
ADV200 SP-...-4-DC
Weight (kg) Weight (lbs)
1015 ... 1055 5,8 12,8 - - -
2075 ... 2150 10,2 22,5 - - -
3185 ... 3220 16,4 36,2 3220 12 26,5
3300 22 48,5 3300 18 39,7
4370 ... 4550 32 70,6 4370 ... 4550 24 52,9
5750 ... 51100 60 132 5750 ... 51100 40 88,2
61320 ... 61600 90 198 61320 ... 61600 68 150
Note ! Weights referred to standard drive with keypad, without options, packaging not included.
Attention