ADV200 SP • Quick start up guide - Specification and installation 73
9.6 Output electrical data
U2 Max output voltage �������������������������� 0,94 x Uln (Uln =AC Input voltage)
f2 Max output frequency ������������������������ 500 Hz (Sizes 1015 ... 61600)
see section 9.3.3 for more details.
Braking IGBT Unit ����������������������������� KBX models: standard internal with external resistor,
KXX: not included;
braking torque 150 % MAX
Maximum voltage imbalance �������������������� 400Vrms, 565
Vpk
Note! In the event of insulation loss, the drive must be immediately disabled and disconnected from power sources..
Sizes Inverter Output Pn mot (Recommended asynchronous motor output)
Heavy duty
(kVA)
Light duty
(kVA)
Heavy duty Light duty
@400
Vac
(kW)
@460Vac
(Hp)
@400Vac
(kW)
@460Vac
(Hp)
1015 1.7 3.0 0.75 1 1.5 2
1022 3.0 4.0 1.5 2 2.2 3
1030 4.0 5.3 2.2 3 3 5
1040 5.3 6.6 3.0 5 4 5
1055 6.6 9 4.0 5 5.5 7.5
2075 9 11.4 5.5 7.5 7.5 10
2110 11.4 15.9 7.5 10 11 15
2150 15.9 21.5 11 15 15 20
3185 21.5 26.3 15 20 18.5 25
3220 26.3 32 18.5 25 22 30
3300 32 43 22 30 30 40
4370 43 52 30 40 37 50
4450 52 60 37 50 45 60
4550 60 73 45 60 55 75
5750 73 104 55 75 75 100
5900 104 125 75 100 90 125
51100 125 145 90 125 110 150
61320 145 173 110 150 132 175
61600 173 208 132 175 160 200
Sizes
I
n Rated output current (For Asynchronous motors)
@U
ln=400Vac @Uln=460Vac
Heavy duty
(A)
Light duty
(A)
Heavy duty
(A)
Light duty
(A)
1015 2.5 4.3 2.3 3.9
1022 4.3 5.8 3.9 5.2
1030 5.8 7.6 5.2 6.8
1040 7.6 9.5 6.8 8.6
1055 9.5 13 8,6 11.7
2075 13 16.5 11.7 14.9
2110 16.5 23 14.9 20.7
2150 23 31 20.7 27.9
3185 31 38 27.9 34.2
3220 38 46 34.2 41.4
3300 46 62 41.4 55.8
4370 62 75 55.8 67.5
4450 75 87 67.5 78.3
4550 87 105 78 94,5
5750 105 150 94.5 135