Wiring of the input and output power terminals
terminal manufacturer.
“5.1.1 Cable Cross Section”,
page 20.
Over-voltage control
In compliance with CSA-requirements Overvoltage at mains terminal is achieved installing an overvoltage
protection device as for :
Type OVR 1N 15 320 from ABB or similar.
Minimum time required for safe DC-link voltage
Before removing drive cover in order to access internal parts, after mains disconnection wait 300 sec for time.
Over-speed; over-load/current limit; motor overload
Drive incorporate over-speed, over-current/current limit, motor overload protection. Instruction manual specify
degree of protection and detailed installation instruction.
Solid State Motor Overload Protection
The drive is not provided with the internal motor overload protection (software function) as required under UL
508c as from 9 May 2013.
The drive is designed for use with motors with integrated thermal overload protection.
on the “digital input connector” terminal, pins 4 and 10, that accepts a maximum of 24
result of this signal is the switching of the motor control device output to solid state OFF.