—————— TPD32-EV ——————
120
5.3.4 START UP procedures
FollowingSTARTUPmenuallowsaquickbasiccommissioningofthedrive.
Speed base value Thisvaluedeterminesthemaxrpmcorrespondingtothemaxsignalappliedtoananalog
input(e.g.10Vor20mA).
Nom ux curr Nominaleldcurrentofthedrive.Settherangethroughthedipswitchesontheregula-
tionboard.Seetable2.4.3.2.
Speed-0 f weak EnablesSpeed-0fweakatzerospeed.
Speed-0 f weak delay Setsatimedelay.
Acc delta … Accelerationramptimesettingonthespeedreference.
Dec delta ... Decelerationramptimesettingonthespeedreference.
Motor data
Inthismenuallthemotorplatedataareplaced.
Incasethespeedself-tuninghastobecarriedout,suchvaluesmustcorrespondtothemotornameplatedata,as
themotortorqueconstantderivesrightfromthem.
note ! Performingthespeedregulatorselftuningthefollowingparametersmustbesetcorrectly
accordingtothemotorused.
Motor nom ux MotornomuxinAmps.
Flux reg mode Fluxregulatormode:constantcurrent(xedeld)orVoltagecontrol.
Full load curr NominalarmaturecurrentinAmps.Itcorrespondstothe100%ofthenominaldriveoutput
current.Thedefaultvalueisthenominaldrivecurrent.Thesettingsforthecurrentlimits(T
current limit parameters)andthe“Overload function”arebasedonthisvalue.
Motor max speed Maximummotorspeedvalue.Setthemotorplatedatavalue.
Max out voltage Maximumarmaturevoltagevalue.WhenFluxregmodeissettodweakening,itcor-
respondstothecrossoverpoint.
Flux weak speed Motor max speed percentagewheretheuxweakeningrangestarts.(Crossoverpoint)
note ! With speed regulator self tuning performed, the above parameters value can be changed.
Limits
Thismenuallowssettingofspeedlimitsvalue,currentlimitsvalueandeldcurrentlimitswhendifferentfrom
thedefaultvaluesinMotor datamenu.
T current limit
ArmaturecurrentlimitvalueaspercentageofFull load curr.Whenoverloadfunctionisused
thisvaluemustbeequalorhigherthanOverload current parametervalue(Overloadfunction).
Flux current max MaximumeldcurrentvalueaspercentageofMotor nom ux.
Flux current min MinimumeldcurrentvalueaspercentageofMotor nom ux.Itcorrespondstothe
Speed-0fweakcurrentvaluewhenSpeed-0fweakfunctionisactiveanditwillbethe
lowereldcurrentlimitvaluewhenthemotorisrunninginVoltagecontrolrange.
Speed min amount Minimumspeedreferencelimit.
Speed max amount Maximumspeedreferencelimit.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the gefran TPD32-EV-500 series and is the answer not in the manual?

gefran TPD32-EV-500 series Specifications

General IconGeneral
Brandgefran
ModelTPD32-EV-500 series
CategoryDC Drives
LanguageEnglish

Related product manuals