GMV5 Home DC Inverter Multi VRF Units
133
If there are walls at four sides of unit, please follow the above-mentioned basic space
requirement;
In principle, if a crown wall (obstacles for keeping out the wind) exists over the machine, a
distance of at least 3000mm should be left between the top of the machine and the crown wall. If
the front, rear, left and right sides of the machine are open spaces, the distance between the top of
the machine and the crown wall should be at least 1500mm. If the requirement for the minimum
1500 mm cannot be met, or the spaces around the machine are not open, an exhaust air duct
needs to be connected to maintain smooth ventilation.