GMV5 Home DC Inverter Multi VRF Units
225
Function Button Name and Meaning
Button
Code
Function Meaning
SW1
UP
Indicates the upward selection button.
SW2
DOWN
Indicates the downward selection button.
SW3
FUNCTION
Indicates the function button, used for function settings.
SW4
CHECK
Indicates the inquiry button, used for function inquiry.
SW5
SKIP
Indicates the skip button.
SW6
BACK
Indicates the return button, used to return to the upper-level menu.
SW7
CONFIRM
Indicates the confirmation button.
SW8
RESET
Indicates the reset button, used to restore factory settings.
5.1.2.2 Introduction to Functions
1)List of functions
Func
tion
Cod
e
Function
Name
Function Meaning
Factory Settings
Remarks
C
o
d
e
Meaning
A2
Refrigerant
recovery
operation
Fully or partially recovers refrigerants in a faulty module
or
—
—
——
It can
only be
set.
A6
Unit
cooling/heati
ng function
Sets the unit to cooling/heating, cooling only, heating only
or air supply mode for centralized management.
n
A
Cooling/heat
ing function
It can be
set and
inquired
A7
Outdoor
silent mode
Sets different silent modes to meet users’ requirements.
1
0
10 kinds of
silent modes
It can be
set and
inquired.
A8
Aftersales
vacuuming
mode
Automatically enables all electronic expansion vlaves and
valves and electromagnetic valves during maintenance to
guarantee vacuum processing in all pipelines.
—
—
——
It can
only be
set.
n0
Conservation
control 1
Automatically decreases the power consumption of the
unit according to system operation parameters.
0
1
No
automatic
conservation
settings.
It can be
set and
inquired.
n3
Forcible
defrosting
operation
Forcibly enables ODU defrosting operation.
—
—
——
It can
only be
set.
n4
Conservation
control 2
Forcibly decreases the maximum power consumption of
the unit
0
0
No capacity
output
limitation
It can be
set and
inquired.