GMV5 Home DC Inverter Multi VRF Units
183
between the IDU and ODU.
(1) Communication cable selection for IDUs/hydro box and wired controller
Total length of
communication
cables of the IDU
and wired controller
L(m)
Number of wire
pieces x wire
diameter (mm
2
)
Common sheath
twisted pair copper
core (RVVS)
The overall
communication length
cannot exceed 250m.
Common shielded
sheath twisted pair
copper core
(RVVSP)
If the unit is installed in
places with strong
electromagnetic
interference, shielded wire
must be used (RVVSP).
Connection between IDU and wired controller is shown as below:
Connection between hydro box and wired controller is shown as below:
(2) Communication cable selection for ODU and IDUs/hydro box
Total length of
communication wire
between indoor unit and
another indoor unit
(outdoor unit): L(m)
Light/Ordinary PVC
sheathed twisted-pair
copper core wire
(RVVS)
If wire size is enlarged to
2×1mm
2
, communication
wire could be longer, but the
total length shall not exceed
1500m.
Shielded light/ordinary
PVC sheathed
twisted-pair copper
core wire (RVVSP)
If unit is installed in a place
with intense magnetic field or
strong interference, it’s
necessary to use shielded
wire (RVVSP).