GMV5 Home DC Inverter Multi VRF Units
319
6. Fix and wire the
electric box.
Put the electric box back to
original position and screw it up.
●Connect all wires.
7. Check and install
the front panels.
●Check the parts and connecting
wires;
If no problem is found, hook the
front panels and tighten the
screws.
Assembly and disassembly of oil separator
Precondition: No refrigerant exists in the pipeline system and the power supply has been disconnected.
Step
Diagram
Operation Instruction
1. Loosen the hooks
at the bottom of the
electric box and the
screws.
●Remove the left and right front
panels and set them aside;
●Loosen the hooks at the bottom
of the electric box.
● Use a screwdriver to unscrew
the electric box.
2. Remove the
electric box.
●Disconnect internal and external
connecting wires of the electric
box.
●Protect the internal parts during
the disassembly.

Table of Contents