GMV5 Home DC Inverter Multi VRF Units
226
Indoor unit
project
number
offset
Prevents IDU project number conflicts when different
refrigerating systems are controlled in a centralized
manner.
Inquire historical fault information of the ODU.
Inquire real-time operation parameters of the ODU.
Indoor unit
project
number
inquiry
Displays address of all IDUs via ODU
Online IDU
quantity
inquiry
Display the quantity of online IDUs.
Outdoor unit
bar code
function
inquiry
Inquire the entire unit bar code and controller barcode of
outdoor unit
2)Description of Functions
(1) A2 Refrigerant recovery operation
This function partially recovers refrigerants in a faulty module or IDU pipeline during unit
maintenance. The refrigerant recovery volume of each basic module is as follows:
Maximum Refrigerant Recovery Volume (kg)
Refrigerant recovery operating mode is refrigerant recovery mode of pipelines of indoor unit.
Refrigerant Recovery
Mode Code
Refrigerant Recovery
Mode Name
Idoor unit pipeline
refrigerant recovery
This mode is selected when an
IDU fails and it is required to
recover refrigerants from the IDU
pipeline.
When this function is enabled, the ODU automatically starts and recovers refrigerants to the
ODU or IDU pipeline.
(2) A6 Unit cooling/heating function
This function sets operation modes of the entire unit, including:
Cooling mode, dry mode, heating mode, floor heating
mode, heating water mode, and air supply mode, etc.
(Notes: the heating/floor heating mode and cooling/dry