mode cannot operate at the same time)
Cooling mode, dry mode, heating water mode, air supply
mode, etc.
Heating mode, floor heating mode, heating water mode,
air supply mode, etc.
(Notes: heating mode and air supply mode cannot
operate at the same time)
The user or administrator can set operation modes of the ODU according to actual situations
to prevent conflicts.
When it is required to set different refrigerating systems to the same functional mode, set the
master system according to the above requirements. For the master system settings, please see
the ―Centralized Control Address DIP Switch (SA2_Addr-CC)‖.
(3) A7 Outdoor silent mode
This function is used when users require lower environment noises, including night-time
automatic silent mode and forcible silent mode.
For the night-time automatic silent mode, the system can automatically judges the highest
daytime environment temperature and then starts silent operations in a certain interval to
guarantee night-time low-noise operation. There are nine types of night-time automatic silent
modes for selection:
Starting the Silent Mode X Hours after the
Daytime Temperature Reaches the Highest
Stopping the Night-time Silent
Mode after Continual Operations
for Y Hours
Low and
medium
noise
mode
Note: The highest daytime temperature is generally in 13:00-15:00.
For the forcible silent mode, the system runs in low-noise mode no matter in the daytime or
night-time. The forcible silent mode fails in three categories:
Low and medium noise
mode
Notes: The system capacity may fall off after the silent mode is set. Therefore, try to balance
the noise with the capacity in selecting a silent mode category. The factory setting is ―00‖.
(4) A8 Aftersales vacuuming mode