number of hydro box – serial
number of shunt valve;
Timer area: engineering number is
on/flickering, the ―number‖ is on.
Notes:
When there is only one hydro box in
the HBS network, skip over the
selection of hydro box and set
directly from serial number of shunt
valve;
If there is no corresponding setting
in P79, then the corresponding
indoor unit engineering number of
shunt valve are all 0, which deems
that the P79 setting is invalid.
Multiple shunt valves are allowed to
match with the same indoor unit
(engineering number), but the same
shunt valve is not allowed to match
with multiple indoor unit
(engineering number);
In the same HBS network, if
corresponding relation setting
between one shunt valve and
indoor unit is valid, then the linkage
setting between indoor unit and
shunt valve is deemed valid;
Enter into the inquiry under ―n4‖
status, temperature area displays
function code and timer area
displays corresponding function
setting value.
Enter into the inquiry under ―A7‖
status, temperature area displays
function code, and timer area
displays corresponding function
setting value.