GMV5 Home DC Inverter Multi VRF Units
72
query, buzzer of the indoor unit operated by the wired
controller will ring until user quits "C01" query or switches to
the next indoor unit.
C03
Indoor unit quantity
query in the system
network
1-80
Timer zone displays the total number of indoor units in the
system.
C06
Preferential
operation query
00: Common
operation
01:
Preferential
operation
Operation method:
In "C06" status, press "MODE" button to enter the interface of
preferential operation query. Press "â–²" or "â–¼" button to select
an indoor unit.
Display mode:
Temperature zone displays the project number of current
indoor unit.
Timer zone displays the preferential operation setting value of
current indoor unit.
C07
Indoor ambient
temperature query
-
Operation method:
In "C07" status, press "MODE" button to enter the interface of
indoor ambient temperature query. Press "â–²" or "â–¼" button to
select an indoor unit.
Display mode:
Temperature zone displays the project number of current
indoor unit
Timer zone displays the temperature value of indoor ambient
temperature sensor after replenishment.
C08
Prompt time query
for air filter
cleaning
4-416: days
Timer zone displays the prompt time for air filter cleaning.
C09
Wired controller
address query
01, 02
Timer zone displays the address of current wired controller.
C11
Indoor unit quantity
query in the case
that one wired
controller controls
many indoor units
1-16
Timer zone displays the total number of indoor units controlled
by the wired controller.
C12
Outdoor ambient
temperature query
-
Timer zone displays the temperature value of the ambient
temperature sensor of master outdoor unit.
C17
Indoor relative
humidity query
20~90
Operation method:
In ―C17‖ status, press ―MODE‖ button to enter the interface of
indoor relative humidity query. Press "â–²" or "â–¼" button to
select an indoor unit.
Display mode:
Temperature zone displays the relative humidity value.
Timer zone displays the project number of indoor unit
(numbers are arranged from small to large).
If HBS network consists of only one indoor unit, the timer zone
will directly display the relative humidity value of that indoor

Table of Contents