GMV5 Home DC Inverter Multi VRF Units
85
mode, energy efficiency test
mode, AHRI test mode); If it is set
to 01, water pump works as
normal.
Setting of static
pressure for DC
fresh air unit
Setting range: 01, 02,
03, 04, 05, 06, 07, 08,
09, 10, 12, 13
There are 13 levels of static
pressure of DC fresh air unit. Each
level is corresponding to a speed
value. After adjusting fan speed at
the main interface of wired
controller, motor speed remains
unchanged. Motor speed can be
changed by setting the static
pressure level upon entering wired
controller functions.
Setting of
system
energy-saving
operation
00: Pleasantness in
priority
01: Energy-saving in
priority
Setting of
defrosting period
40: 40 minutes
50: 50 minutes
60: 60 minutes
00: Common
01: Forcible defrosting
After setting is finished, it
automatically restores to "00".
Setting of the
highest capacity
output limitation
for outdoor unit
Enter query in "n4" status.
Temperature zone displays the
function code and timer zone
displays the corresponding setting
value.
Quiet function
for outdoor unit
00: No quiet function
01~09: Intelligent
nighttime quiet mode 1
to mode 9
10~12: Forcible quiet
mode 1 to mode 3
Enter query in "A7" status.
Temperature zone displays the
function code and timer zone
displays the corresponding setting
value.
Note:
(1) In parameter setting status, "Fan" and "Timer" buttons are invalid. By pressing "ON/OFF"
button, user can return to the main interface but not power on or off the unit.
(2) In parameter setting status, signals of remote controller are invalid.