Technical Data
Voltage rating
0(2)…11 V (default)
Current rating
max. ±1 mA
Resolution
8 bit
Accuracy
±150 mV
Zero output voltage
< 200 mV
Protection
Short-circuit protected;
protected against failure
voltage (24 VAC, 40 VDC)
Feedback signal
Auto/manual mode and output
value
Table 47 Analog output modules data
Output status LEDs behavior
Automatic mode
Brightness follows the
commanded output signal
Override mode
Flashes
Table 48 Analog output status LED behavior
Modules with Manual Overrides
The CLIOPR822A/CLIOLR822A Analog Output Modules are
equipped with manual overrides: one rotary knob for each
analog output.
The manual overrides can be set manually to either "auto"
or "0…110 %" (infinitely adjustable).
NOTICE
Damage to the electronic module!
Do not use a tool to adjust the rotary knobs.
Do not use excessive force. Adjust only by hand.
Analog Outputs Configured as Binary Outputs
Using CARE, the analog outputs can be configured
individually as binary outputs. The voltage output is then 0 V
or 10 V, depending upon the signal from the controller.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Excel 800 LION and is the answer not in the manual?

Honeywell Excel 800 LION Specifications

General IconGeneral
BrandHoneywell
ModelExcel 800 LION
CategoryControl Systems
LanguageEnglish

Related product manuals