Excel 800 LION
9 EN1B-0375GE51 R0308
Interfaces and Bus Connections
The Excel 800 LION System can be connected to the
following devices and systems:
Panel Bus
For communication with up to 16 Panel Bus I/O modules
Polarity-insensitive
L
ON
W
ORKS
Bus
For communication with other L
ON
W
ORKS
Bus devices
within the building
FTT10, link power compatible
Polarity-insensitive
C-Bus
For communication with other controllers, e.g., existing
Excel 500 Controllers
HMI
For connecting an operator interface, e.g., XI582 or a
laptop, e.g., for CARE
Modem
For connecting a modem or an ISDN terminal adapter
Technical Data
System Data
Operating voltage 24 VAC, ± 20 %, 21 … 30 VDC
Max. number of C-Bus
participants
30
Power consumption Max. 3.57 A
(1 CLLIONLC01 Controller
+ 16 I/O modules)
Push-in terminals 1.5 mm
2
Overvoltage protection All inputs and outputs are
protected against 24 VAC and
40 VDC overvoltage as well as
against short-circuiting.
Calculated lifetime of
weakest component
MTBF
13.7 years
Table 7 System data
Standards
Protection class IP20
Product standard EMC
EN 60730-2-9:2005-10
Testing electrical
components
IEC68
Certification CE
System transformer
The system transformer(s) must
be safety isolating transformers
according to IEC 61558-2-6.
In the U.S.A. and Canada, NEC
Class 2 transformers must be
used.
Low-Voltage Device
Safety Assessment
EN 60730-1:2005-12,
EN 60730-2-9:2005-10
Table 8 Standards
Operational Environment
Ambient operating
temperature
0 … 50 °C (32 … 122 °F)
Ambient operating
humidity
5 … 93 % rel. humidity
(non-condensing)
Ambient storage
temperature
–20 … 70 °C (–4 … +158 °F)
Ambient storage
humidity
5 … 95 % rel. humidity
(non-condensing)
Vibration under
operation
0.024” double amplitude
(2 … 30 Hz),
0.6 g (30 … 300 Hz)
Dust, vibration According to EN60730-1:2005-12
RFI, EMI According to EN60730-1:2005-12
Table 9 Operational environment

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Excel 800 LION and is the answer not in the manual?

Honeywell Excel 800 LION Specifications

General IconGeneral
BrandHoneywell
ModelExcel 800 LION
CategoryControl Systems
LanguageEnglish

Related product manuals