Excel 800 LION
EN1B-0375GE51 R0308
68
Troubleshooting
Testing Wiring Connections
The push-in terminals feature small holes (1 mm in
diameter) which can be used to measure the signals.
Insert a probe (1) as shown on the right.
Fig. 96 Testing wiring connections
Troubleshooting on the CLLIONLC01 Controller
The following LEDs of the CLLIONLC01 Controller can be used for troubleshooting purposes:
Power LED (green)
Alarm LED (red)
L
ON
W
ORKS
service LED
C-Bus Tx and Rx LEDs
HMI Tx and Rx LEDs
Modem Interface Tx and Rx LEDs
Power LED (green)
case Power LED Meaning Remedy
1 ON
Normal operation No action necessary
2 Flashing
One or more of the internal voltage supplies
are outside of the permissible ranges. The
controller stops operation.
Check power
Check wiring
If problem persists, replace hardware
3 Goes out briefly
The operator has activated the reset button
The controller is performing a warm start
No action necessary
Table 68 CLLIONLC01 power LED

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Excel 800 LION and is the answer not in the manual?

Honeywell Excel 800 LION Specifications

General IconGeneral
BrandHoneywell
ModelExcel 800 LION
CategoryControl Systems
LanguageEnglish

Related product manuals