Excel 800 LION
EN1B-0375GE51 R0308
62
LON Software Interface Description
Overview
LonTalk Protocol
Excel 800 LION L
ON
W
ORKS
Bus I/O Modules use a L
ON
T
ALK
protocol communication with other nodes on the L
ON
W
ORKS
network, with commissioning tools und supervisory devices.
Features
• Network variables for communications between nodes,
but no explicit messages
• Configuration network variables
• L
ON
M
ARK
FPT protocol for downloading an Excel 800
LION L
ON
W
ORKS
Bus I/O Module firmware via LON:
loadable apbG file (supported by CARE and EXCELON)
Addressing, binding, and commissioning
Excel 800 LION L
ON
W
ORKS
Bus I/O Modules are addressed,
bound, and commissioned using CARE or any other
standard L
ON
W
ORKS
commissioning tool based on LNS 2.0
and higher, e.g., LonMaker for Windows.
Configuration
Excel 800 LION L
ON
W
ORKS
Bus I/O Modules are configured
using CARE.
CLIOL821A Analog Input Module
For the CLIOL821A Analog Input Module the L
ON
M
ARK
Profile 520 "Analog Input" has been assigned per input.
Each input object has its own configuration properties,
except for heartbeat configuration, which will be shared
among all objects.
Fig. 89 L
ON
M
ARK
analog input object
Input types and corresponding NVs
Input type NV used
NTC10kΩ
NTC20kΩ
PT1000-1
NI1000TK5000
PT3000
BALCO500
nvoAiTempP
PT1000-2 nvoAiTemp
0(2)…10V nvoAiValuePct
Slow binary input nvoAiSwitch
Other Sensors
Sensor break/short circuit
INVALID
Table 60 Input types and corresponding NVs
Transmission/Updates
These variables are transmitted immediately when their
value has been changed by a higher rate than the
configured "send on delta" (default: 0.3 K).
These variables are also transmitted as heartbeat output
(default: 60 sec) on a regular basis as dictated by the
maximum send time (nciSndHrtBt) configuration variable.