Service LED of I/O Modules
case Service LED Meaning Remedy
1
LED remains OFF after
power-up
If the power LED is also OFF, then
Defective device hardware
Possible power supply problems, clock
problems, defective processor
Replace hardware
2
LED is lit continuously after
first power-up
L
ON
W
ORKS
Bus I/O modules:
Defective hardware
Panel Bus I/O modules:
I/O module has not yet been configured
by CLLIONLC01
Boot loader is active
Failure during last firmware download
Checksum error
L
ON
W
ORKS
Bus I/O modules:
Replace hardware
Panel Bus I/O modules:
Set the hex address to the position configured
with CARE
Ensure that I/O Bus switch S2 of CLLIONLC01
Controller is set to position "Panel"
Check the Panel Bus wiring:
- Check for cable breaks
- Check for cable short-circuits
- If using separate transformers: Check ground
connection
Eliminate any mixture of Panel Bus I/Os and
LonWorks I/Os on same wire
Allow CLLIONLC01 to configure I/O module
Unplug and replug the module
If problem persists, replace hardware
3
Alternating flash between
service LED and power LED
Panel Bus I/O modules, only:
Download error or application checksum error.
Boot loader is running
Panel Bus I/O modules, only:
Wait until rebooting (firmware download) has
been completed
4
LED flashes at power up,
goes OFF, and then is lit
continuously
L
ON
W
ORKS
Bus I/O modules, only:
L
ON
W
ORKS
Bus I/O module lacks application
Download application
5
LED repeatedly blinks
ON for 1 sec and
OFF for 1 sec
L
ON
W
ORKS
Bus I/O modules, only:
L
ON
W
ORKS
Bus I/O module is unconfigured, but
has an application
Set module to configured mode
6
LED remains OFF after a
short ON duration
I/O module is configured and running normally
No action necessary
7
LED flashes continuously in
following pattern:
4 x ON/OFF followed by
pause
Sensor failure of analog input module
(in case of L
ON
W
ORKS
Bus I/O modules, this
behavior can occur only if the appropriate NV
has been bound)
Check sensor or connection
Check sensor configuration
8
LED flashes continuously in
following pattern:
5 x ON/OFF followed by
pause
L
ON
W
ORKS
Bus I/O modules, only: L
ON
W
ORKS
I/O Bus module has received the wink
command from network, physical outputs are
unaffected
No action necessary
9
LED flashes continuously in
following pattern:
6 x ON/OFF followed by
pause
Boot loader problem or hardware defect
Replace hardware
10
LED flashes continuously in
following pattern:
7 x ON/OFF followed by
pause
Communications failure
Check bus wiring
Ensure that I/O Bus switch S2 of CLLIONLC01
Controller is set to correct position
Ensure that L
ON
W
ORKS
Bus I/O modules and
Panel Bus I/O modules are not sharing same
bus
In case of Panel Bus I/O modules, only:
Check for incorrect HEX addresses (2 Panel Bus
I/O modules using same HEX address)
In case of L
ON
W
ORKS
Bus I/O modules, only:
Check heartbeat
Table 75 Service LED of I/O modules

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Excel 800 LION and is the answer not in the manual?

Honeywell Excel 800 LION Specifications

General IconGeneral
BrandHoneywell
ModelExcel 800 LION
CategoryControl Systems
LanguageEnglish

Related product manuals