Excel 800 LION
69 EN1B-0375GE51 R0308
Alarm LED (red)
Case Alarm LED Meaning Remedy
1 OFF
Normal operation No action necessary
2 ON
Watchdog alarm output is powered
The controller has encountered a
hardware problem
- or -
The application has a fault
- or -
The controller has been powered up
without an application or the operator
has manually stopped the application,
e.g., using XL-Online.
In this case, the LED will light up
13 minutes after power-up without
application
Try powering down and then
powering up the CLLIONLC01.
If problem persists, check and – if
necessary – reload the application.
If problem still persists, replace
hardware
3 Flashing
Although the controller has encountered a
problem, the watchdog alarm output has not
yet been powered.
If problem persists, the LED will become lit
constantly, see case #2.
The controller performs a warm start.
If it happens only once, the controller
has performed a restart
If, however, it happens multiple times,
then there is an application or hardware
problem (see case #2)
Table 69 CLLIONLC01 alarm LED

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Excel 800 LION and is the answer not in the manual?

Honeywell Excel 800 LION Specifications

General IconGeneral
BrandHoneywell
ModelExcel 800 LION
CategoryControl Systems
LanguageEnglish

Related product manuals