4.2.3 Angle Requirements
The inverter can be wall-mounted or support-mounted. The installation angle
requirements are as follows:
● Install the inverter vertically or at a maximum back tilt of 15 degrees to
facilitate heat dissipation.
● Do not install the inverter at forward tilted, excessive backward tilted, side
tilted, horizontal, or upside down positions.
Figure 4-5 Installation angle
4.3 Tools
Type
Tool
Instal
lation
tools
Hammer drill
Drill bit: Ф8
mm, Ф6 mm
Flat-head
insulated torque
screwdriver
Phillips
insulated torque
screwdriver
Hex insulated
torque
screwdriver
SUN2000-(8K, 10K)-LC0 Series
User Manual 4 Installation
Issue 01 (2023-09-15) Copyright © Huawei Digital Power Technologies Co., Ltd. 27