EasyManuals Logo

Kaco Powador 30.0 TL3 M/XL User Manual

Kaco Powador 30.0 TL3 M/XL
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #10 background imageLoading...
Page #10 background image
Technical Data
Page  Operating Instructions for Powador .-. TL_EN
ENEN
 Technical Data
. Electrical data
Input levels 30.0 TL3 33.0 TL3 36.0 TL3 39.0 TL3
Recommended power range of the generator [kW] 33.75 37.12 40.5 44.95
MPP@Pnom from [V] to [V] 350 ... 800
Operating range from [V] to [V] 200 ... 800
Starting voltage [V]* 250
No-load voltage (U
OC max
) [V]
1,000
Max. input current [A] 3 x 34.0
Max. power per MPP tracker [W] 20,000
Number of DC connections 3 x 1 (M) / 3 x 4 (XL)
Number of MPP controls 3
max. short-circuit current (I
SC max
) [A]
3x 34.0 3x 40.8 3x 40.8 3 x 34.0
max. input source feedback current [A] 0
Polarity safeguard Short-circuit diode
Output levels
Rated power [VA] 25,000 27,500 30,000 33,300
Grid voltage [V] 400 / 230 (3/N/PE)
Rated current [A] 3 x 36.2 3 x 39.9 3 x 45.5 3 x 48.3
Initial short-circuit alternating current
(lk” rst single period eective value) [A]
49.3
Start-up current [A] 98
Rated frequency [Hz] 50/60
cos phi 0.80 inductive ... 0.80 capacitive
Number of feed-in phases 3
Distortion factor (THD) [%] < 3
General electrical data
Max. eciency [%] 98.0
European eciency [%] 97.8
Self consumption: standby [W] < 30
Self consumption: night [W] ~1.5
Feed-in starts at [W] 120
Circuit design IGBT, self-commutated, transformerless
Grid monitoring Country-specic
CE conformity Yes
Table 1: Electrical data

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kaco Powador 30.0 TL3 M/XL and is the answer not in the manual?

Kaco Powador 30.0 TL3 M/XL Specifications

General IconGeneral
BrandKaco
ModelPowador 30.0 TL3 M/XL
CategoryInverter
LanguageEnglish

Related product manuals