Mounting
Page Operating Instructions for Powador .-. TL_EN
ENEN
Authorised electrician
For safe transportation of the inverter, use a transportation pallet.
Figure : Transportation of the inverter
Mounting
DANGER
Risk of fatal injury from re or explosions
Fire caused by ammable or explosive materials in the vicinity of the inverter can lead to serious
injuries.
› Do not mount the inverter in an area at risk of explosion or in the vicinity of highly ammable mate-
rials.
Installation location
• As dry as possible, climate-controlled, with the waste heat dissipated away from the inverter
• Air circulation should not be blocked
• When installing the unit in a control cabinet, provide forced ventilation so that the heat is suciently dissipated
• Close to the ground, accessible from the front and sides without requiring additional resources
• Protected on all sides against heavy rain and direct sunlight (thermal heating) in outdoor areas.
Implementation where necessary via constructional measures, e.g. wind breaks.
• For easy operation, ensure during installation that the display is slightly below eye level.
Floor and wall
• With sucient load-bearing capacity
• Accessible for installation and maintenance
• Made from heat-resistant material (up to °C),
• Flame resistant
• Minimum clearances to be observed during assembly: see Figure on page .
NOTE
Access by maintenance personnel for service
Any additional costs arising from unfavourable structural or mounting conditions shall be billed to
the customer.