19
BASIC SAFETY INSTRUCTIONS
Short-circuit resistance
The drive converters are conditional short-circuit proof. After resetting the internal pro-
tective devices the intended function is guaranteed.
Exceptions:
Repeatedly occurring ground faults or short-cicuits at the input can lead to the de-
vective of the unit.
The COMBIVERT F5-AIC is not short-circuit proof at the mains input in case of an
error or in status nOP! Conditional protection at the mains input is possible with a
semiconductor fuse.
The short-circuit protection at the DC output must be ensured by external aR or gR
fuses.
Switching an the input
Forapplicationsthatrequirecyclicswitchingo󰀨andonofthedriveconverter,maintain
ano󰀨-timeofatleast5minafterthelastswitchon.Ifyourequireshortercycletimes
please contact KEB Automation KG.
1.6 Maintenance
The following maintenance work has to be carried out when required, but at least once
per year by authorized and trained personnel.Check unit for loose screws and plugs and
tighten if necessary.
Check system for loose screws and plugs and tighten if necessary.
Clean drive converter from dirt and dust deposits. Pay attention especially to coo-
lingnsandprotectivegridofthefans.
Examineandcleanextractedairlterandcoolingairlterofthecontrolcabinet.
Check the function of the fans of the drive converter. The fan must be replaced in
case of audible vibrations or squeak.
In the case of liquid-cooled drive converters a visual test of the cooling circuit for
leaks and corrosion must be carried out.The cooling circuit must be completely
emptyifaunitshallbeswitchedo󰀨foralongerperiod.Thecoolingcircuitmustbe
blown out additionally with compressed air at temperatures below 0°C.
1.7 Repair
In case of malfunction, unusual noises or smells inform a person in charge!
DANGER
Unauthorized exchange, repair and modications!
Unpredictable malfunctions!
The function of the drive converter is dependent on its parameteri-
zation. Never replace without knowledge of the application.
ModicationorrepairispermittedonlybyKEBAutomationKGau-
thorized personnel.
Only use original manufacturer parts.
Infringement will annul the liability for resulting consequences.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KEB COMBIVERT 19F5 Series and is the answer not in the manual?

KEB COMBIVERT 19F5 Series Specifications

General IconGeneral
BrandKEB
ModelCOMBIVERT 19F5 Series
CategoryInverter
LanguageEnglish

Related product manuals