4 Unit Data
Information on the dimensioning => „Dimensioning“.
Device size 14 16 18 20 22
Housing size E G H R R
Cooling mode (L=air; W=water) L L L L L W
Input data
Mains phases 3
Permitted mains forms
1)
TN system
Rated input voltage U
N / V 400
Input voltage range U
in / V 340…480 ± 0%
Mains frequency f
N / Hz 50 / 60 ± 2
Rated input power S
N / kVA 11 23 35 52 80
Rated input current I
N / A 16.5 33 50 75
2)
115
2)
Max. permissible mains fuse type gR / aR
25 50 80 100 160
Output data
Rated output voltage U
outN_dc / V 680
Output voltage range
3)
U_dc / V 530…840
Overvoltageswitch-o󰀨(E.OP) U
OP_dc / V 840
Power supply/regenerative rated current
4)
IoutN_dc / A 16.5 33 50 75 115
Max. regenerative DC current 30 s I
out_max_dc / A 29.7 49.5 75 112 172 207
Rated switching frequency
5)
fSN / kHz 8
Max. switching frequency f
S_max / kHz 16
Other data (referring to the rated data)
Overcurrentcut-o󰀨(E.OC) I
OC / % 216 180 180 180 180 216
Overload current (E.OL) 30 s I
OL / % 180 150 150 150 150 180
Max. permissible DC link capacity C
ext / mF 50 50
Max. AIC charging current (=> 6.5) I
AIC / A 29
6)
57 29 226 226
Max. external charging current (=> 6.5) I
ext / A 75
6)
135 322
Max. permissible total charging current (=> 6.5)
Ipre / A 104
6)
192 351 226 226
Mains input circuit (=> 6.5) Type A1 A2 A1 D1
Permissible DC fuses => „DC fuses“
Short-circuit factor at the connection point (S
kn / SN) 15 < S
kn“ < 350
Power dissipation at rated operation P
BR / W 295 449 525 830 1400
Max. heat sink temperature t
_max / °C 90 90 90 90 90 60
Table 7: Device data
1)
Operation on a local limited IT system with sine-wave EMC lter is possible.
2)
The input current of the drive converter is limited, if necessary to the rated current of the AIC / LCL
lter.
3)
The operation is dependent on the voltage setpoint and the UOP limit (=> Programming manual).
4)
Measured at a reference voltage of 680 V DC.
5)
Must be set to 8 kHz for AIC operation (factory setting 4 kHz) !
6)
At ambient temperature Ta of 45°C.
27
UNIT DATA

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KEB COMBIVERT 19F5 Series and is the answer not in the manual?

KEB COMBIVERT 19F5 Series Specifications

General IconGeneral
BrandKEB
ModelCOMBIVERT 19F5 Series
CategoryInverter
LanguageEnglish

Related product manuals