TP-7070 7/18112 Section 5 Accessories
Fault and Status Condition
Fault
LED
System Monitoring LEDs and Functions
System
Ready LED
Generator
Running LED
Communications
Status LED
Common
Fault LED
Common
Fault
Output
Horn
Overcrank (Shutdown) Red SF Red SF Off Green Red SF On On
High Engine Temperature (Warning) Yellow SF Red SF Green Green Red SF On On
High Engine Temperature (Shutdown) Red SF Red SF Off Green Red SF On On
Low Oil Pressure (Warning) Yellow SF Red SF Green Green Red SF On On
Low Oil Pressure (Shutdown) Red SF Red SF Off Green Red SF On On
Overspeed (Shutdown) Red SF Red SF Off Green Red SF On On
Emergency Stop Red SF Red SF Off Green Off On On
Low Coolant Level/Aux (Shutdown) Red SF Red SF Off Green Red SF On On
Low Coolant Temperature Yellow SF Red SF Green or Off Green Red SF On On
Low Fuel Yellow SF Red SF Green or Off Green Red SF On On
Low Cranking Voltage Yellow SF Red SF Off Green Red SF On On
Battery Charger Fail Yellow SF Green Green or Off Green Off On On
Battery Voltage (Hi) Yellow SF Green Green or Off Green Off On On
Battery Voltage (Lo) Yellow SF Green Green or Off Green Off Off Off
Common Fault (Warning) Yellow SF Green Green or Off Green Red SF On Off
Common Fault (Shutdown) Red SF Green Green or Off Green Red SF On On
User Input #1 (Warning) Yellow SF Green Green or Off Green Off Off Off
User Input #1 (Shutdown) Red FF Green Green or Off Green Off On On
User Input #2 (Warning) Yellow SF Green Green or Off Green Off Off Off
User Input #2 (Shutdown) Red FF Green Green or Off Green Off On On
User Input #3 (Warning) Yellow SF Green Green or Off Green Off Off Off
User Input #3 (Shutdown) Red FF Green Green or Off Green Off On On
User Input #4 (Warning) Yellow SF Green Green or Off Green Off Off Off
User Input #4 (Shutdown) Red FF Green Green or Off Green Off On On
User Input #5 (Warning) Yellow SF Green Green or Off Green Off Off Off
User Input #5 (Shutdown) Red FF Green Green or Off Green Off On On
ATS Position N (RSA III with ATS only) Green Green Green or Off Green Off Off Off
ATS Position E (RSA III with ATS only) Red Red SF Green or Off Green Off Off Off
ATS Available N (RSA III with ATS only) Green Green Green or Off Green Off Off Off
ATS Available E (RSA III with ATS only) Red Red SF Green or Off Green Off Off Off
ATS Fault (RSA III with ATS only) Yellow SF ??? Green or Off Green Off Off On
ATS Fault (RSA III with ATS only) Red FF Red SF Green or Off Green Off Off On
EPS Supplying Load Green Green Green or Off Green Off Off Off
Not-In-Auto Red FF Red SF Off Green Red SF On On
Communication Status (Loss - Master) Red FF Off Off Red FF Off On On
Communication Status (Loss - Slave) Red SF Off Off Red SF Off On On
Note: SF = Slow Flash (1 second intervals), FF = Fast Flash (200 millisecond intervals)
Figure 5-16 System Monitoring LEDs and Functions

Table of Contents