Basic units in the power range of 15 ... 90 kW
Terminal assignment - Application I/O PT E82ZAFA...
7
Extensions for automation
7.4
7.4.5
L
7.4-13
EDS82EV903-1.0-11/2002
7.4.5 Terminal assignment - Application I/O PT E82ZAFA...
l The device is wired using an attachable terminal block for larger cable
cross-sections. The function module stands out approx. 13 mm because of
the attachable terminal block.
l The application I/O PT is wired like the application I/O.
l Please note: The application I/O PT has got one terminal 7 (GND) only.
Electrical connection Plug connector with spring connection
Possible connections
rigid: 1.5 mm
2
(AWG 16)
flexible:
without wire crimp cap
1.5 mm
2
(AWG 16)
with wire crimp cap,without plastic sleeve
1.5 mm
2
(AWG 16)
with wire crimp cap, with plastic sleeve
0.5 mm
2
(AWG 20)
Bare end 9mm
Data of the spring-clamp
terminals
Show/Hide Bookmarks

Table of Contents

Other manuals for Lenze 8200 vector

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze 8200 vector and is the answer not in the manual?

Lenze 8200 vector Specifications

General IconGeneral
CategoryDC Drives
Series8200 vector
Enclosure RatingIP20
Control MethodVector control
CommunicationCANopen, DeviceNet, Profibus
Protection FeaturesOvercurrent, overvoltage, undervoltage, overtemperature, short circuit
Humidity< 95 % non-condensing
Operating Temperature0 to +45 °C (derating above 40°C)

Related product manuals