General data/application conditions
4
Technical data
4.2
L
4.2-1
EDS82EV903-1.0-11/2002
4.2 General data/application conditions
Conformity CE Low-Voltage Directive (73/23/EEC)
Approvals UL 508C Unde rwriter Laboratories (File-No. E132659)
Power Conversion Equipment
Max. permissible motor
cable length
For rated mains voltage and chopper frequency of 8 kHz without additional output
filters
shielded 50 m
For com
liance with EMC re
ulations, the
ermissible
unshielded 100 m
,
cable lengths must be changed
Vibration resistance Acceleration resistance up to 0.7g (Germanischer Lloyd, general conditions)
Climatic conditions Class 3K3 to EN 50178 (without condensation, average relat ive humidit y 85 %)
Degree of pollution VDE 0110 part 2 pollution degree 2
Packaging (DIN 4180) Dust packaging
Permissible temperature
ranges
Transport -25°C...+70°C
Storage -25°C...+60°C
Operation -10°C...+55°C above +40 °C the rated output current is to be reduced by
-10°C...+50°C
(o nl y 8200 ve ct o r
15 ... 90 k W)
2.5 %/°C
Permissible installation
height
0 ... 4000 m amsl above 1000 m amsl the rat e d output current is t o be
reduced by 5 %/1000 m
Mounting positions vertical
Mounting clearances
above/below ≥100 mm
to the sides Side-by-side mounting with a distance of 3 mm
DC group operation possible, except E82EV251K2C and E82EV371K2C
Standards and application
conditions