Error elimination
Maloperation of the drive
11
Troubleshooting and fault elimin ation
11.4
11.4.1
L
11.4-1
EDS82EV903-1.0-11/2002
11.4 Error elimination
11.4.1 Maloperation of the drive
Fault Cause Remedy
Motor d oes not rotate DC-bus voltage too low
(Red LED is blinking ever y 0.4 s;
keypad display
LU)
Check mains voltage
Controller inhibited
(Green LED is blinking, keypad display:
c)
Remove the controller inhibit, controller inhibit can be set
through several sources
Automatic start inhibited (C0142 = 0 or 2) LOW-HIGH signal a t X3/28
If necessary, correct start condition (C0142)
DC injection brake active (DCB) Deactivate DC injection brake
Mechanical motor brake is not released Manual or electrical release of mechanical motor brake
Quick stop (QSP) active (keypad display: c) Remove quick stop
Setpoint = 0 Setpoint selection
JOG setpoint activated and JOG frequency = 0 JOG setpoint selection (C0037 ... C0039)
Active fault Eliminate f ault
Wrong parameter set active Change to correct parameter set via terminal
Control mode C0014 = -4- , -5-, but no motor parameter identification Moto r paramete r identificati o n (C0148)
Unde r C0410 several functions, which exclude each other, are assigned
to the same signal source.
Correct configuration in C0410
Use internal voltage source X3/20 for function modules Standard I/O,
INTERBUS, PROFIBUS-DP or LECOM-B (RS485):
Bridge between X3/7 and X3/39 is missing
Bridge terminals
Motor d oes not rotate Defective motor cable Check motor cable
M
o
t
o
r
d
o
e
s
n
o
t
r
o
t
a
t
e
smoothly
Maximum current set t o o low (C0022, C0023) Adaptation to the application
y
Motor underexcited or overexcited Check parameter setting (C0015, C0016, C0014)
C0084, C0087, C0088, C0089, C0090, C0091 and/or C0092 are not
adapted to the motor data
Manual adaptation or identification of motor parameters
(C0148)
Current consumption of Sett ing of C0016 to o high Correct setting
C
u
r
r
e
n
t
c
o
n
s
u
m
p
t
o
n
o
f
motor too high
Sett ing of C0015 too lo w Correct setting
g
C0084, C0087, C0088, C0089, C0090, C0091 and/or C0092 are not
adapted to the motor data
Manual adaptation or identification of motor parameters
(C0148)
Motor rotates, setpoints are
“0”
With the function j of the keypad a setpoint has been selected. Set the setpoint to ”0” by C0140 = 0
Motor parameter
d
e
n
t
f
c
a
t
o
n
s
t
o
p
s
w
t
h
Motor t oo small compared with rated power
identification stops with
error LP1
DC brake active via terminal
Unacceptable drive response
with vector control
various Vector control o ptimisation ( 8.4-4)
Torque dip in the field
weakening range
various Contact Lenze
Stalling of the motor when
operatinginthefield
weakening range
Show/Hide Bookmarks

Table of Contents

Other manuals for Lenze 8200 vector

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze 8200 vector and is the answer not in the manual?

Lenze 8200 vector Specifications

General IconGeneral
BrandLenze
Model8200 vector
CategoryDC Drives
LanguageEnglish

Related product manuals