EDS84DMOTPBUS EN 3.0 - 11/2011 L 63
Communication manual 8400 motec PROFIBUS
Parameter data transfer
PROFIdrive parameter data channel (DP-V1)
9.3.4 Error codes
Error code Description Explanation Additional
information
0x0000 Impermissible parameter
number
Access to unavailable parameter -
0x0001 Parameter value cannot be
changed
Change access to a parameter value that cannot be
changed
Subindex
0x0002 Lower or upper value limit
exceeded
Change access with value beyond the value limits Subindex
0x0003 Faulty subindex Access to unavailable subindex Subindex
0x0004 No array Access with subindex to non-indicated parameter -
0x0005 Wrong data type Change access with value that does not match the
data type of the parameter
-
0x0006 No setting permitted (only
resettable)
Change access with value unequal to 0 where this is
not permitted
Subindex
0x0007 Description element cannot
be changed
Change access to a description element that cannot
be changed
Subindex
0x0008 Reserved (PROFIdrive profile V2: PPO-Write requested in the IR
is not available)
-
0x0009 Description data not
available
Access to unavailable description (parameter value is
available)
-
0x000A Reserved (PROFIdrive profile V2: Wrong access group) -
0x000B No parameter change rights Change access without parameter change rights -
0x000C Reserved (PROFIdrive profile V2: Wrong password) -
0x000D Reserved (PROFIdrive profile V2: Text in the cyclic traffic
cannot be read)
-
0x000E Reserved (PROFIdrive profile V2: Name in the cyclic traffic
cannot be read)
-
0x000F No text array available Access to unavailable text array (parameter value is
available)
-
0x0010 Reserved (PROFIdrive profile V2: Missing PPO-Write) -
0x0011 Request cannot be executed
due to the operating state
Access is not possible due to temporary reasons not
specified here
-
0x0012 Reserved (PROFIdrive profile V2: Other error) -
0x0013 Reserved (PROFIdrive profile V2: date in the cyclic traffic
cannot be read)
-
0x0014 Value impermissible Change access with the value that is inside the value
limits but not permissible for other permanent
reasons (parameters with defined individual values)
Subindex
0x0015 Response too long The length of the current response exceeds the
maximum transmittable length
-
0x0016 Parameter address
impermissible
Impermissible or non-supported value for attribute,
number of subindices, parameter number, or
subindex, or a combination
-
0x0017 Format impermissible Write request: Impermissible or non-supported
format of parameter data
-
0x0018 Number of values not
consistent
Write request: Number of values of the parameter
data do not match the number of subindices in the
parameter address
-
0x0019 Reserved - -
...
0x0064

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze E84DGFCp Series and is the answer not in the manual?

Lenze E84DGFCp Series Specifications

General IconGeneral
BrandLenze
ModelE84DGFCp Series
CategoryConference System
LanguageEnglish

Related product manuals