EDS84DMOTPBUS EN 3.0 - 11/2011 L 81
Communication manual 8400 motec PROFIBUS
Parameter reference
Communication-relevant parameters of the operating system
13 Parameter reference
This chapter complements the parameter list and table of attributes in the software
manual and the »Engineer« online help for the Inverter Drive 8400 motec by the
parameters for the PROFIBUS communication.
13.1 Communication-relevant parameters of the operating system
This chapter lists the communication-relevant parameters of the 8400 motec operating
system in numerically ascending order.
C01501
C01503
Software manual/»Engineer« online help "Inverter Drive 8400 motec"
Here you can find general information on parameters.
Parameter | Name:
C01501 | Resp. to communication error with MCI
Data type: UNSIGNED_8
Index: 23074
d
= 5A22
h
Configuration of monitoring functions for the communication unit
Selection list
0 No Reaction
1Fault
4 WarningLocked
Subcodes Lenze setting Info
C01501/1 1: Fault Resp. to MCI error 1
• Response to a communication error.
C01501/2 1: Fault Resp. to MCI error 2
• Response to an incompatible communication unit.
; Read access ; Write access CINH PLC-STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C01503 | MCI timeout
Data type: UNSIGNED_16
Index: 23072
d
= 5A20
h
Setting range (min. value | unit | max. value)
0 ms 1000
Subcodes Lenze setting Info
C01503/1 200 ms MCI timeout
; Read access ; Write access CINH PLC-STOP No transfer COM MOT Scaling factor: 1