EDS84DMOTPBUS EN 3.0 - 11/2011 L 71
Communication manual 8400 motec PROFIBUS
Monitoring
Settings and displays in the »Engineer«
10.3 Settings and displays in the »Engineer«
For monitoring the PROFIBUS communication, you can set a Lenze-internal monitoring
time (C13881
) and a response of the controller (C13880) in the »Engineer« via the
Monitoring tab.
The watchdog monitoring time defined in the PROFIBUS master is displayed in code
C13882
.
If the controller does not receive any valid process data when being in the
"Data_Exchange" state, the process data are handled according to the setting in
C13885
. (The last data sent by the master can either be used or set to zero.)
Moreover, you can set the error responses in the controller that cause a setting of the
external diagnostic bit ("Diag-Bit") (C13886
).