Communication manual 8400 motec PROFIBUS
Technical data
General data and operating conditions
18 L EDS84DMOTPBUS EN 3.0 - 11/2011
4 Technical data
4.1 General data and operating conditions
Hardware manual "Inverter Drives 8400 motec"
Here you will find the ambient conditions and information on the
electromagnetic compatibility (EMC) that also apply to the communication unit.
Area Values
Order designation • E84DGFCPxNx (PROFIBUS)
• E84DGFCPxJx (PROFIBUS + Safety)
Communication profile • PROFIBUS DP-V0 (DRIVECOM)
• PROFIBUS DP-V1 (PROFIdrive), from SW version 2.0
Standards / specifications • IEC 61158 / EN 50170
• IEC 61784
Communication medium RS485
Interface for communication • PROFIBUS input: M12 pins, 5-pole, B-coded
• PROFIBUS output: M12 socket, 5-pole, B-coded
Max. cable length 1200 m (depending on the selected baud rate, the used cable type and
hardware (repeaters))
Bus termination Bus terminating resistors are required at the first and last PROFIBUS node
(implemented in the connector of the bus cable)
Network topology • Line (without repeater)
• Tree/line (with repeater)
Type of station PROFIBUS slave
Number of slave stations • Max. 31 (without repeater)
• Max. 125 (with repeater)
PNO identification number 0x0A89
Baud rate for cable type A (EN 50170) 9.6 kbps ... 12 Mbps (automatic detection)
External voltage supply • U = 24 V DC (20 V - 0 % ... 29 V + 0 %)
•I
max
= 400 mA
Conformities, approvals • CE
•UR / cUR