Owner’s & Installation Manual 27
ENGLISH
Move to Low Ambient Heating Operation
setting by pressing button.
4
Press button to setup Low
Ambient Heating Operation.
5
Press button to save.
8
Move FAN Speed Setting during
Emergency Heater Operation by pressing
button.
6
Press button to setup FAN
Speed during Emergency Heater
Operation.
7
0 : not use
1 : use - compressor off(0℉/ -18℃) / compressor on(5℉ / -15℃)
2 : use - compressor off(5℉ / -15℃) / compressor on(10℉ / -12℃)
3 : use - compressor off(10℉/ -12℃) / compressor on(15℉ / -9℃)
0 : fan off
1 : fan on
ƓEmergency heater operation in Low Ambient temperature
- compressor off : Emergency heater enabled
- compressor on : Emergency heater disabled
Pressing the button will exit
the settings mode. If is not
pressed, the remote controller will
automatically exit setup mode after 25
seconds with no input. If the set button is
not pressed, the changes will not take
effect.
9
26 New Wide Wired Remote Controller
Installation Instructions Installation Instructions
Installer Setting - Option Function Setting
Function Code Existing condition
Select existing condition
of each mode by pressing
button.
(00: not installed,
01 : installed)
3
Press button to save.
4
If pressing button repeatedly, it moves to
the selected option function code as pictured
below.
2
Function
Plasma purification
Electric heater
Humidifier
Elevation grill
Ventilation kit
Auxiliary heater
Code
20
21
22
23
24
25
Pressing the button will exit
the settings mode. If is not
pressed, the remote controller will
automatically exit setup mode after 25
seconds with no input. If the set button is
not pressed, the changes will not take
effect.
5
1
Pressing and holding the button for
3 seconds enters the remote
controller setup mode. If it is
not held for 3 seconds, it enters
the user setup mode.
Setting feature for indoor unit when Plasma purification / Electric heater / Humidifier / Elevation grill
Ventilation kit / Auxiliary heater is newly installed, or installed unit is removed.

Table of Contents

Other manuals for LG MultiV Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LG MultiV Series and is the answer not in the manual?

LG MultiV Series Specifications

General IconGeneral
BrandLG
ModelMultiV Series
CategoryRemote Control
LanguageEnglish

Related product manuals