EasyManuals Logo
Home>LG>Remote Control>MultiV Series

LG MultiV Series User Manual

LG MultiV Series
38 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #5 background imageLoading...
Page #5 background image
Owner’s & Installation Manual 9
ENGLISH
8 New Wide Wired Remote Controller
Installation Instructions
Installer Setting Code Table
1) General air-conditioner product
Some contents may not be displayed depending on the product function
Installation Instructions
If the installation is not done correctly it can cause injury to the user or damage to your property.
Installation must be done by a certified HVAC technician, and any problems arising from improper
installation are the owner’s financial responsibility.
CAUTION
Installer Setting - How to enter installer setting mode
Function Code Value
Pressing and holding the button for
3 seconds enters the remote controller
setup mode. If it is not held for 3
seconds, it enters the user setup mode.
- If pressing once shortly, it enters into
user setup mode. Please press more
than 3 seconds for sure.
1
When you enter the setting mode
initially, Function code is displayed on
the bottom of the LCD screen.
2
No. Function Code Value
1 Test Run 01 01:Set
2 Address Setting 02 00~FF : Address
<ESP Step> <ESP Value> <Example>
01:VeryLow 0 ~ 255
02:Low
3 E.S.P. Value 03
03:Med
04:High
05:Very High
01:Remo
4 Thermistor 04 02:Indoor
03:2TH
01:Low
02:Med
5 Ceiling Height 05
03:High
04:Very High
01:V-H
02:F-H
6 Static Pressure 06
03:V-L
04:F-L
7 Master Setting 07
00:Slave
※ If only “Plus1” series models 00 : Group setting
01:Master
01 : Single setting
8 Override Setting 08
00:Slave
01:Master
9 Dry Contact 09
00:Auto-Off
01:Auto-On
10
Release 3 Min.
10 01:Set
Delay
11 Zone State 11
01:Variable
02:Fixed
12
Celsius
12
00:Celsius
(Optimized only for U.S.A)
Fahrenheit Switching 01:Fahrenheit
13 Zone Type 13
00:Zone Controller
01:Damper Controller
14 Zone Number 14 02~04(Zone number)
Emergency Heater
15
Setting
18
16 Plasma 20
17 Electric heater 21
18 Humidifier 22
00: Not Installed
19 Elevation Grill 23
01: Installed
20 Ventilation Kit 24
21 Auxiliary Heater 25
22
Static Pressure
32
00: use static pressure (code 06) set value
Step 01~ 11: static pressure step (code 32) set value
Function Code ESP valueESP step
Some categories of the menu may not be displayed according to the function of the
product, or the menu name may be different.
Select mode Setup Low Ambient Heating Operation Setup FAN Speed
00 : not use 0 : not use 0 : fan off
01 : use 1 : use – compressor off(0℉/-18℃)/on(5℉/-15℃) 1 : fan on
2 : use – compressor off(5℉/-15℃)/on(10℉/-12℃)
3 : use – compressor off(10℉/-12℃)/on(15℉/-9℃)

Table of Contents

Other manuals for LG MultiV Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LG MultiV Series and is the answer not in the manual?

LG MultiV Series Specifications

General IconGeneral
BrandLG
ModelMultiV Series
CategoryRemote Control
LanguageEnglish

Related product manuals