V6R VRF 50/60Hz
100
Midea
V6R
Series Service Manual
2.11 zF6: Electronic expansion valve connection error
Digital display output
Description
1F6 indicates Electronic expansion valve A connection error.
2F6 indicates Electronic expansion valve C connection error.
All units stop running.
Error code is displayed on the unit with the error.
Trigger / recover condition
Trigger condition: The main control board cannot receive the feedback signal of EEV.
Recover condition: The main control board can receive the feedback signal of EEV.
Reset method: When the main control board can receive the feedback signal of EEV, F6 flashes, a manual system restart
is required before the system can resume operation.
Possible causes
Electronic expansion valve coil not connected properly or has malfunction.
Outdoor main PCB damaged.