Electronic expansion valve (EEV)
(Set the controller to display E0, default)
Rotating Defrosting Operation
Timing of rotating defrosting operation:
Te<-2°C and T4<20°C , and either of the points below is met:
There is an obviously drop in the temperature of outdoor unit heat exchanger outlet
Cumulative operating time after the latest defrosting control arrives an hour
Switching action of two-module parallel system heat exchanger
Figure 3-7.2: Switching action of two-module parallel system heat exchanger
Condition E
Total defrosting control time has reached 5 minutes.
T3 >Target value for a certain time.
Notes:
1. This function is only available when the indoor units connected in V6R system are 2nd generation AC VRF indoor units (which will be released soon) or 2nd
generation DC VRF indoor units produced after May 31st, 2020 only (The package of upgraded indoor units will add yellow label on both sides to distinguish
the indoor units before and after the upgrade).