Series Service Manual
1 Error Code Table
Table 6-1.1: Outdoor Error code table
Manual re-start
required
2
Communication error between outdoor units
Only displayed on the slave unit with
the error
Communication error between MS and master unit
Only displayed on the master unit with
the error
T3/T4 temperature sensor error
Abnormal power supply voltage
Discharge temperature sensor error (T7C1)
Outdoor unit address error
EEPROM mismatch of compressor
T6B temperature sensor error
T6A temperature sensor error
Electronic expansion valve connection error
T5 temperature sensor error
T8 temperature sensor error
T9 temperature sensor error
TL temperature sensor error
T7 temperature sensor error
Communication error between main board and
compressor drive board
Qty. of outdoor unit decreases error
Only displayed on the master unit with
the error
Qty. of outdoor unit increases error
Only displayed on the master unit with
the error
Compressor inverter module protection
Low pressure protection lock out (P2 3X in 60 minutes)
Compressor discharge temperature protection ( P4 3X in
100 minutes)
Qty. of indoor units mismatching
High pressure sensor error
DC fan module protection ( P9 10X in 120 minutes)
Low pressure sensor error
Slave unit malfunction(y=1,2 ,1Hd stands for slave unit 1
error)
Only displayed on the master unit with
the error
Compressor inverter module temperature protection ( PL
3X in 100 minutes)
Primary current protection
Secondary current protection
Discharge temperature protection or discharge
temperature switch protection
Compressor inverter module temperature protection
Compressor discharge insufficient superheat protection
Table continued on next page …