1.2 Modes Set on Main PCB
1.2.1 Night silent mode setting
Night silent mode is activated X hours after the peak daytime temperature, and is deactivated after Y hours, where X and Y
are as specified in Table 4-1.2.
Table 4-1.2: Night silent time setting
Night silent time is 6h/10h (default)
Night silent time is 6h/12h
Night silent time is 8h/10h
Night silent time is 8h/12h
Figure 4-1.2: Night silent mode example (default setting, 6h/10h)
1.2.2 Silent mode setting
Different silent mode can be set by switch ENC5. In night silent mode, silent mode and super silent mode, the Max. outdoor
fan speed and the compressor frequency are limited.
Table 4-1.3: Silent mode setting
Silent mode (limit max. fan speed and compressor frequency)
Super silent mode (limit max. fan speed and compressor frequency)
Set silent mode via centralized controller
Notes:
1. Max. fan speed and compressor frequency refers to Table 3-8.3 in Part 3, 8.4 “Silent Mode”.
Night silent
mode activated
The outdoor unit senses the peak daytime
outdoor ambient temperature
Night silent mode
deactivated